Induction Motor Control Theory.
Induction Motor Design
has a major effect on the behaviour and performance
of an induction motor. Very often the details or class of design of a
motor are not well understood or promoted.
i) Stator design.
The stator is the outer body of the motor which houses
the driven windings on an iron core. In a single speed three phase motor
design, the standard stator has three windings, while a single phase motor
typically has two windings.
The stator core is made up of a stack of round
pre-punched laminations pressed into a frame which may be made of
aluminium or cast iron. The laminations are basically round with a
round hole inside through which the rotor is positioned. The inner
surface of the stator is made up of a number of deep slots or grooves
right around the stator. It is into these slots that the windings
are positioned. The arrangement of the windings or coils within the
stator determines the number of poles that the motor has.
A standard bar magnet has two poles, generally known as North and
South. Likewise, an electromagnet also has a North and a South pole.
As the induction motor Stator is essentially like one or more electromagnets
depending on the stator windings, it also has poles in multiples of
two. i.e. 2 pole, 4 pole, 6 pole etc. |
|
The number of poles determines the speed of the induction
motor. A two pole motor has a synchronous speed of 3000 RPM at 50Hz and
3600RPM at 60Hz. A four pole motor runs at half this speed, a six pole
motor at one third speed and an eight pole motor at one quarter speed.
The winding configuration, slot configuration and lamination steel all
have an effect on the performance of the motor. The voltage rating of
the motor is determined by the number of turns on the stator and the power
rating of the motor is determined by the losses which comprise copper
loss and iron loss, and the ability of the motor to dissipate the heat
generated by these losses.
The stator design determines the rated speed of the motor and most of
the full load, full speed characteristics.
Top of Motor Control Page
| Motor Control
Forum
ii) Rotor Design.
The Rotor comprises a cylinder made up of round laminations
pressed onto the motor shaft, and a number of short-circuited windings.The
rotor windings are made up of rotor bars passed through the rotor, from
one end to the other, around the surface of the rotor. The bars protrude
beyond the rotor and are connected together by a shorting ring at each
end. The bars are usually made of aluminium or copper, but sometimes made
of brass. The position relative to the surface of the rotor, shape, cross
sectional area and material of the bars determine the rotor characteristics.
Essentially, the rotor windings exhibit inductance and resistance, and
these characteristics can effectively be dependant on the frequency of
the current flowing in the rotor.
A bar with a large cross sectional area will exhibit a low resistance,
while a bar of a small cross sectional area will exhibit a high resistance.
Likewise a copper bar will have a low resistance compared to a brass bar
of equal proportions.
Positioning the bar deeper into the rotor, increases the amount of iron
around the bar, and consequently increases the inductance exhibited by
the rotor. The impedance of the bar is made up of both resistance and
inductance, and so two bars of equal dimensions will exhibit a different
A.C. impedance depending on their position relative to the surface of
the rotor. A thin bar which is inserted radialy into the rotor, with one
edge near the surface of the rotor and the other edge towards the shaft,
will effectively change in resistance as the frequency of the current
changes. This is because the A.C. impedance of the outer portion of the
bar is lower than the inner impedance at high frequencies lifting the
effective impedance of the bar relative to the impedance of the bar at
low frequencies where the impedance of both edges of the bar will be lower
and almost equal.
The rotor design determines the starting characteristics.
iii) Equivalent Circuit.
The induction motor can be treated essentially as
a transformer for analysis. The induction motor has stator leakage reactance,
stator copper loss elements as series components, and iron loss and magnetising
inductance as shunt elements. The rotor circuit
likewise has rotor leakage reactance, rotor copper (aluminium) loss and
shaft power as series elements.
The transformer in the centre of the equivalent circuit can be eliminated
by adjusting the values of the rotor components in accordance with the
effective turns ratio of the transformer.
From the equivalent circuit and a basic knowledge of the operation of
the induction motor, it can be seen that the magnetising current component
and the iron loss of the motor are voltage dependant, and not load dependant.
Additionally, the full voltage starting current of a particular motor
is voltage and speed dependant, but not load dependant.
The magnetising current varies depending on the design of the motor. For
small motors, the magnetising current may be as high as 60%, but for large
two pole motors, the magnetising current is more typically 20 - 25%. At
the design voltage, the iron is typically near saturation, so the iron
loss and magnetising current do not vary linearly with voltage with small
increases in voltage resulting in a high increase in magnetising current
and iron loss.
Top of Motor Control Page
| Motor Control
Forum
iv) Starting
Characteristics.
In order to perform useful work, the induction motor
must be started from rest and both the motor and load accelerated up to
full speed. Typically, this is done by relying on the high slip characteristics
of the motor and enabling it to provide the acceleration torque.
Induction motors at rest, appear just like a short circuited transformer,
and if connected to the full supply voltage, draw a very high current
known as the "Locked Rotor Current". They also produce torque
which is known as the "Locked Rotor Torque". The Locked
Rotor Torque (LRT) and the Locked
Rotor Current (LRC) are a function of the
terminal voltage to the motor, and the motor design. As the motor accelerates,
both the torque and the current will tend to alter with rotor speed if
the voltage is maintained constant.
The starting current of a motor, with a fixed voltage, will drop very
slowly as the motor accelerates and will only begin to fall significantly
when the motor has reached at least 80% full speed. The actual curves
for induction motors can vary considerably between designs, but the general
trend is for a high current until the motor has almost reached full speed.
The LRC of a motor can range from 500% Full Load Current
(FLC) to as high as 1400% FLC. Typically, good motors fall in the range
of 550% to 750% FLC.
The starting torque of an induction motor starting with a fixed voltage,
will drop a little to the minimum torque known as the pull up torque
as the motor accelerates, and then rise to a maximum torque known as the
breakdown or pull out torque at almost full speed and then
drop to zero at synchronous speed. The curve of start torque against rotor
speed is dependant on the terminal voltage and the motor/rotor design.
The LRT of an induction motor can vary from as low as 60% Full
Load Torque (FLT) to as high as 350% FLT.
The pull-up torque can be as low as 40% FLT and the breakdown torque can
be as high as 350% FLT. Typical LRTs for medium to large motors are in
the order of 120% FLT to 280% FLT.
The power factor of the motor at start is typically 0.1
- 0.25, rising to a maximum as the motor accelerates, and then falling
again as the motor approaches full speed.
A motor which exhibits a high starting current, i.e. 850% will generally
produce a low starting torque, whereas a motor which exhibits a low starting
current, will usually produce a high starting torque. This is the reverse
of what is generally expected.
The induction motor operates due to the torque developed by the interaction
of the stator field and the rotor field. Both of these fields are due
to currents which have resistive or in phase components and reactive or
out of phase components. The torque developed is dependant on the interaction
of the in phase components and consequently is related to the I2R
of the rotor. A low rotor resistance will result in the current being
controlled by the inductive component of the circuit, yielding a high
out of phase current and a low torque.
Figures for the locked rotor current and locked rotor torque are almost
always quoted in motor data, and certainly are readily available for induction
motors. Some manufactures have been known to include this information
on the motor name plate. One additional parameter which would be of tremendous
use in data sheets for those who are engineering motor starting applications,
is the starting efficiency of the motor. By the starting efficiency of
the motor, I refer to the ability of the motor to convert amps into newton
meters. This is a concept not generally recognised within the trade, but
one which is extremely useful when comparing induction motors. The easiest
means of developing a meaningful figure of merit, is to take the locked
rotor torque of the motor (as a percentage of the full load torque) and
divide it by the locked rotor current of the motor (as a percentage of
the full load current).
i.e
Starting
efficiency = |
Locked
Rotor Torque |
|
Locked Rotor Current |
If the terminal voltage to the motor is reduced while it is starting,
the current drawn by the motor will be reduced proportionally. The torque
developed by the motor is proportional to the current squared, and so
a reduction in starting voltage will result in a reduction in starting
current and a greater reduction in starting torque. If the start voltage
applied to a motor is halved, the start torque will be a quarter, likewise
a start voltage of one third will result in a start torque of one ninth.
v) Runnng Characteristics.
Once the motor is up to speed, it operates at low slip,
at a speed determined by the number of stator poles.The frequency of the
current flowing in the rotor is very low. Typically, the full load slip
for a standard cage induction motor is less than 5%. The actual full load
slip of a particular motor is dependant on the motor design with typical
full load speeds of four pole induction motor varying between 1420 and
1480 RPM at 50 Hz. The synchronous speed of a four pole machine at 50
Hz is 1500 RPM and at 60 Hz a four pole machine has a synchronous speed
of 1800 RPM.
The induction motor draws a magnetising current while it is operating.
The magnetising current is independent of the load on the machine, but
is dependant on the design of the stator and the stator voltage. The actual
magnetising current of an induction motor can vary from as low as 20%
FLC for large two pole machines to as high as 60% for small eight pole
machines. The tendency is for large machines and high speed machines to
exhibit a low magnetising current, while low speed machines and small
machines exhibit a high magnetising current. A typical medium sized four
pole machine has a magnetising current of about 33% FLC.
A low magnetising current indicates a low iron loss, while a high magnetising
current indicates an increase in iron loss and a resultant reduction in
operating efficiency.
The resistive component of the current drawn by the motor while operating,
changes with load, being primarily load current with a small current for
losses. If the motor is operated at minimum load, i.e. open shaft, the
current drawn by the motor is primarily magnetising current and is almost
purely inductive. Being an inductive current, the power factor is very
low, typically as low as 0.1. As the shaft load on the motor is increased,
the resistive component of the current begins to rise. The average current
will noticeably begin to rise when the load current approaches the magnetising
current in magnitude. As the load current increases, the magnetising current
remains the same and so the power factor of the motor will improve. The
full load power factor of an induction motor can vary from 0.5 for a small
low speed motor up to 0.9 for a large high speed machine.
The losses of an induction motor comprise: iron loss, copper loss, windage
loss and frictional loss. The iron loss, windage loss and frictional losses
are all essentially load independent, but the copper loss is proportional
to the square of the stator current. Typically the efficiency of an induction
motor is highest at 3/4 load and varies from less than 60% for small low
speed motors to greater than 92% for large high speed motors. Operating
power factor and efficiencies are generally quoted on the motor data sheets.
Top of Motor Control Page
| Motor Control
Forum
vi) Design Classification.
There are a number of design/performance classifications
which are somewhat uniformly accepted by different standards organisations.
These design classifications apply particularly to the rotor design and
hence affect the starting characteristics of the motors. The two major
classifications of relevance here are design A, and design B.
Design A motors have a shallow bar rotor, and are characterised by a very
high starting current and a low starting torque. Typical values are 850%
current and 120% torque. Shallow bar motors usually have a low slip, i.e.
1480 RPM.
Design B motors have a deeper bar rotor and are characterised by medium
start current and medium starting torque. Typical design B values are
650% current and 180% torque. The slip exhibited by design B motors is
usually greater than the equivalent design A motors. i.e. 1440 RPM.
Design F motors are often known as Fan motors having a high rotor resistance
and high slip characteristics. The high rotor resistance enables the fan
motor to be used in a variable speed application where the speed is reduced
by reducing the voltage. Design F motors are used primarily in fan control
applications with the motor mounted in the air flow. These are often rated
as AOM or Air Over Motor machines.
Top of Motor Control Page
| Motor Control
Forum
vii) Frame Classification.
Induction motors come in two major frame types, these
being Totally Enclosed Forced air Cooled (TEFC),
and Drip proof.
The TEFC motor is totally enclosed in either an aluminium or cast iron
frame with cooling fins running longitudinally on the frame. A fan is
fitted externally with a cover to blow air along the fins and provide
the cooling. These motors are often installed outside in the elements
with no additional protection and so are typically designed to IP55 or
better.
Drip proof motors use internal cooling with the cooling air drawn through
the windings. They are normally vented at both ends with an internal fan.
This can lead to more efficient cooling, but requires that the environment
is clean and dry to prevent insulation degradation from dust, dirt and
moisture. Drip proof motors are typically IP22 or IP23.
Top of Motor Control Page
| Motor Control
Forum
viii) Temperature
Classification.
There are two main temperature classifications applied
to induction motors. These being Class B and Class F.The temperature class
refers to the maximum allowable temperature rise of the motor windings
at a specified maximum coolant temperature.
Class B motors are rated to operate with a maximum coolant temperature
of 40 degrees C and a maximum winding temperature rise of 80 degrees C.
This leads to a maximum winding temperature of 120 degrees C.
Class F motors are typically rated to operate with a maximum coolant temperature
of 40 degrees C and a maximum temperature rise of 100 degrees C resulting
in a potential maximum winding temperature of 140 degrees C.
Operating at rated load, but reduced cooling temperatures gives an improved
safety margin and increased tolerance for operation under an overload
condition. If the coolant temperature is elevated above 40 degrees C then
the motor must be derated to avoid premature failure. Note: Some Class
F motors are designed for a maximum coolant temperature of 60 degrees
C, and so there is no derating necessary up to this temperature.
Operating a motor beyond its maximum, will not cause an immediate failure,
rather a decrease in the life expectancy of that motor. A common rule
of thumb applied to insulation degradation, is that for every ten degree
C rise in temperature, the expected life span is halved. Note: the power
dissipated in the windings is the copper loss which is proportional to
the square of the current, so an increase of 10% in the current drawn,
will give an increase of 21% in the copper loss, and therefore an increase
of 21% in the temperature rise which is 16.8 degrees C for a Class B motor,
and 21 degrees C for a Class F motor. This approximates to the life being
reduced to a quarter of that expected if the coolant is at 40 degrees
C. Likewise operating the motor in an environment of 50 degrees C at rated
load will elevate the insulation temperature by 10 degrees C and halve
the life expectancy of the motor.
Top of Motor Control Page
| Motor Control
Forum
ix) Power factor
correction
Power factor correction is achieved by the addition
of capacitors across the supply to neutralise the inductive component
of the current. The power factor correction may be applied either
as automatic bank correction at the main plant switchboard, or as static
correction installed and controlled at each starter in such a fashion
that it is only in circuit when the motor is on line.
Automatic bank correction consists of a number of banks of
power factor correction capacitors, each controlled by a contactor which
in turn is controlled by a power factor controller. The power factor controller
monitors the supply coming into the switchboard and adds sufficient capacitance
to neutralise the inductive current. These controllers are usually set
to adjust the power factor to 0.9 - 0.95 lagging. (inductive)
Static correction is controlled by a contactor when the motor is started
and when the motor is stopped. In the case of a Direct On Line starter,
the capacitors are often controlled by the main DOL contactor which is
also controlling the motor. With static correction, it is important that
the motor is under corrected rather than over corrected. This is because
the capacitance and the inductance of the motor form a resonant circuit.
While the motor is connected to the supply, there is no problem. Once
the motor is disconnected from the supply, it begins to decelerate. As
it decelerates, it generates voltage at the frequency at which it is rotating.
If the capacitive reactance equals the inductive reactance, i.e. unity
power factor, we have resonance. If the motor is critically corrected
(pf = 1) or over corrected, then as the motor slows, the voltage it is
generating will pass through the resonant frequency set up between the
motor and the capacitors. If this happens, major problems can occur. There
will be very high voltages developed across the motor terminals and capacitors
causing insulation damage, high resonant currents can flow, and transient
torque's generated can cause mechanical equipment failure.
The correct method for sizing static correction capacitors, is to determine
the magnetising current of the motor being corrected, and connect sufficient
capacitance to give 80% current neutralisation. Charts and formula based
on motor size alone can be totally erroneous and should be avoided if
possible. There are some power authorities who specify a fixed amount
of KVAR per kilowatt, independent of the size or speed. This is a dangerous
practice. More information on power factor correction
Top of Motor Control Page
| Motor Control
Forum
x) Single phase motors.
In order for a motor to develop a rotating torque in
one direction, it is important that the magnetic field rotates in one
direction only. In the case of the three phase motor, there is no problem
and the field follows the phase sequence. If voltage is applied to a single
winding, there are still multiples of two poles which alternate between
North and South at the supply frequency, but there is no set rotation
for the vectors. This field can be correctly considered to be two vectors
rotating in opposite directions. To establish a direction of rotation
for the vector, a second phase must be added. The second phase is applied
to a second winding and is derived from the first phase by using the phase
shift of a capacitor in a capacitor start motor, or inductance and resistance
in an induction start motor. (sometimes known as a split phase motor.)
Small motors use techniques such as a shaded pole to set the direction
of rotation of the motor.
More information on Single Phase Motors
Top of Motor Control Page
| Motor Control
Forum
xi) Slip Ring Motors.
Slip ring motors or wound rotor motors are a variation
on the standard cage induction motors. The slip ring motor has a set of
windings on the rotor which are not short circuited, but are terminated
to a set of slip rings for connection to external resistors and contactors.
The slip ring motor enables the starting characteristics of the motor
to be totally controlled and modified to suit the load. A particular high
resistance can result in the pull out torque occurring at almost zero
speed providing a very high locked rotor torque at a low locked rotor
current. As the motor accelerates, the value of the resistance can be
reduced altering the start torque curve in a manner such that the maximum
torque is gradually moved towards synchronous speed. This results in a
very high starting torque from zero speed to full speed at a relatively
low starting current. This type of starting is ideal for very high inertia
loads allowing the machine to get to full speed in the minimum time with
minimum current draw.
The down side of the slip ring motor is that the sliprings and brush assemblies
need regular maintenance which is a cost not applicable to the standard
cage motor. If the rotor windings are shorted and a start is attempted,
i.e the motor is converted to a standard induction motor, it will exhibit
an extremely high locked rotor current, typically as high as 1400% and
a very low locked rotor torque, perhaps as low as 60%. In most applications,
this is not an option.
Another use of the slipring motor is as a means of speed control. By modifying
the speed torque curve, by altering the rotor resistors, the speed at
which the motor will drive a particular load can be altered. This has
been used in winching type applications, but does result in a lot of heat
generated in the rotor resistors and consequential drop in overall efficiency.
More information on Slip Ring Motors
xii) Direction of
Rotation.
The direction that a three phase induction motor rotates
is determined by the direction of the rotation of the stator field.
The Direction is therefore determined by the rotation of the three phases
applied to the motor. To reverse the direction of rotation of an induction
motor, interchange two phases connected to the motor.
Supply |
Motor |
L1 |
R |
L2 |
S |
L3 |
T |
To reverse, change to:
Supply |
Motor |
L2 |
R |
L1 |
S |
L3 |
T |
To reverse the direction of a single phase winding, reverse
the connections to one winding only. i.e. reverse the connections to the
run winding but not the start winding.
Top of Motor Control Page
| Motor Control
Forum
Single Phase
Motors
Single Phase
Motor Connection diagrams
50Hz motors on 60Hz
60Hz motors on 50Hz
Motor Starting methods
Induction Motor Calculations
|